How to choose the right thermal relay?

Author: Shenzhen Yuan Zhi Electronics Co., Ltd.Time:2018-03-01 16:26:58Views:1030SML

How to properly select and use a thermal relay is an old topic. However, many units have still occasioned the accidental burning of the motor due to unreasonable selection or use of the thermal rela...
label:
How to properly select and use a thermal relay is an old topic. However, many units have still occasioned the accidental burning of the motor due to unreasonable selection or use of the thermal relay.

Thermal relay bimetal, fusible alloy, thermistor, thermal magnetic and many other kinds, are based on the use of current thermal effect of a protective relay made, widely used in motor overload protection Therefore, the selection and use of thermal relays in addition to comply with the general provisions, but also pay attention to the following points:

1. Star / delta start control circuit, the thermal relay installation location is different, the selection of the thermal relay specifications are not the same: the main circuit thermal relay string in the total line when the current setting value should be protected motor rated current The same value, the main circuit in the thermal relay string delta running circuit in the setting value should be protected motor rated current value of 1 / 1.732.

2. Thermal relays generally have manual reset and automatic reset two reset forms.

This relay, thermal relay use two kinds of reset the form of conversion, by adjusting the reset screw to complete the thermal relay factory, the manufacturer generally set to automatically reset state. In use, the thermal relay should be set to manual reset or automatic reset state according to the specific circumstances of the control loop. Under normal circumstances, should follow the thermal relay protection action even if the thermal relay automatically reset, be protected relay, thermal relay motor selection should not be automatically restarted principle, otherwise the thermal relay should be set to manual reset state.

This is to prevent the motor from restarting the damaged equipment several times after the fault has not been cleared. (For example, pushbutton controlled manual start and manual stop control circuits are usually used. The thermal relay can be set to auto reset mode. The automatic start circuit with automatic component control should set the thermal relay to manual reset mode.

3. For thermal relays with different rated current levels but the same thermal element adjustment range (for example, thermal relays of the JR16 series have a thermal element setting of 14A-16A for both thermal relays rated at 20A and 60A Adjustment range) of the selection, should check the thermal relay used in the ambient temperature and the motor is protected ambient temperature.

When the thermal relay ambient temperature is higher than the protected motor ambient temperature above 15 ℃, you should use relays, thermal relays use larger rated current level thermal relay; when the thermal relay ambient temperature is lower than the motor to be protected When the ambient temperature is below 15 ℃, use a smaller one rated current thermal relay.

4. For repeated short-time work motor overload protection, the test should be repeated in the field, relays, thermal relays used to adjust the selection can be more reliable protection. The first method is to set the thermal relay setting current slightly lower than the rated current of the motor. If it is found to be constantly operating during operation, gradually adjust the setting value of the thermal relay until it meets the operation requirements.